Siemens Auxiliary Contact, 1 Contact, 1 NO, 3RH1, Snap-On, 10 A, 690V, 3RH1921-2CA10

Subtotal (1 unit)*

$24.48

(exc. GST)

$26.93

(inc. GST)

Add to Basket
Select or type quantity
In Stock
  • Plus 1 unit(s) shipping from 09 November 2026
  • Plus 50 unit(s) shipping from 09 November 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +$24.48

*price indicative

RS Stock No.:
392-8951
Mfr. Part No.:
3RH1921-2CA10
Brand:
Siemens
Find similar products by selecting one or more attributes.
Select all

Brand

Siemens

Number of Contacts

1

Product Type

Auxiliary Contact

Normal State Configuration

1 NO

Series

3RH1

Mount Type

Snap-On

Contact Current

10A

Terminal Type

Cage Clamp

Pole and Throw Configuration

1P

Contact Voltage

690V

Mounting Location

Front

Rated Insulation Voltage Ui

690V

Operational Current Ie

10A

Mechanical Durability

10Mcycles

Minimum Operating Temperature

-25°C

Maximum Operating Temperature

60°C

Standards/Approvals

IEC 60947-5-1, IEC 60947-4-1

COO (Country of Origin):
CZ

Siemens 3RH1 Series Auxiliary Contact, 1P Pole Configuration, 1NO Normal State Configuration - 3RH1921-2CA10


This auxiliary contact is a front-mounted Snap-on switch designed for use with compatible contactors. It interfaces with 3RT1 contactors to provide an additional instantaneous normally open contact for signalling or control circuits. The unit operates across a wide ambient range and meets relevant IEC standards for control and power contact devices.

Features and Benefits:


• 690V Rated insulation voltage provides high-voltage compatibility
• 10A Contact current supports common control-circuit loads
• Mechanical durability 10M cycles ensures extended service life
• Spring-type terminals allow secure, vibration-resistant connection
• IP20 Front protection permits safe operator access in enclosures

Applications


• Suitable for use with 3RT10 contactors
• Ideal for front-panel status signalling in control cabinets
• Used with 3RT145 contactors for auxiliary switching tasks
• Can be used for interlock feedback to motor starters

What Terminal connection method does it use?


It uses spring-loaded terminals that accept solid or stranded conductors 0.5 to 2.5 mm².

What short-circuit protection is recommended for the auxiliary circuit?


A 10A characteristic miniature circuit-breaker or a 10A gG fuse at 500V, 1kA is specified.

What operational current can it handle at AC-15, 230V?


It can carry up to 6A under AC-15 utilisation at 230V.

How does it perform at low temperatures during operation?


It is rated for continuous operation down to -25°C.

Which standards govern its mirror-contact and safety functions?


It complies with IEC 60947-4-1 for mirror-contact use and IEC 60947-5-1 for control-device requirements.