- RS Stock No.:
- 230-9480
- Mfr. Part No.:
- RDN211002
- Brand:
- GEORGIN
7 In Global stock for delivery within 10 working day(s)
Added
Price (ex. GST) 1 Box of 1
$503.97
(exc. GST)
$554.37
(inc. GST)
Box(es) | Per Box |
1 + | $503.97 |
- RS Stock No.:
- 230-9480
- Mfr. Part No.:
- RDN211002
- Brand:
- GEORGIN
Technical data sheets
Legislation and Compliance
- COO (Country of Origin):
- FR
Product Details
The galvanically insulated interface is an associated intrinsic safety item of equipment that is installed in a safe zone or in zone 2 in an IP 54 housing, thanks to the Ex nA protection mode. Its mission is to limit the level of energy that may appear in an electric circuit routed through a potentially explosive area, whatever the connection established upstream.
In addition to its energy-limiting function, its facilitates the use of signals in safe areas (e.g., relays), converts signals (e.g., 4/20 mA to 0-10V) or duplicates signals. Other functions are also available, such as the threshold relay or powering intrinsic safety.
Intrinsic safe relay
Input: 2 x switch or proximity sensor
Output: 1 x relay (SPST) per channel
Option: without, clamp terminals
Power supply: 24/48 Vdc
DIN rail mounting housing
Input: 2 x switch or proximity sensor
Output: 1 x relay (SPST) per channel
Option: without, clamp terminals
Power supply: 24/48 Vdc
DIN rail mounting housing
ATEX / IECEx informations:
EC type examination certificate LCIE 02 ATEX 6104X
IECEx LCI09.0013X certificate
[Ex ia] IIC (-20 °C < Ta < 60 °C)
Group II (surface) - category (1) G/D
Installation in safe zone
Barrier for equipment installed in zone 0,1,2 et 20,21,22
See leaflet for a safe use
EC type examination certificate LCIE 02 ATEX 6104X
IECEx LCI09.0013X certificate
[Ex ia] IIC (-20 °C < Ta < 60 °C)
Group II (surface) - category (1) G/D
Installation in safe zone
Barrier for equipment installed in zone 0,1,2 et 20,21,22
See leaflet for a safe use
Specifications
Attribute | Value |
---|---|
Number of Channels | 2 |
Barrier Type | Galvanic Barrier |
Maximum Voltage | 12V |
Hazardous Area Certification | ATEX |
Maximum Current | 25mA |
Supply Voltage | 24V dc |
Maximum Operating Temperature | +60°C |
Minimum Operating Temperature | -20°C |
Series | RDN |
Operating Temperature Range | -20°C to 60°C |