CA8220 Power Analyser
The CA8220 is optimised for maintenance and troubleshooting of electrical equipment, electrical systems and in single phase and balance three phase systems.,The CA8220 includes measurements for testing and monitoring rotating machines in operation. including temperature, current , duration of in-rush current, resistance of windings and rotation speed.
Large backlit 173-segment LCD display.
Power measurement up to 250kW (dependant on clamp selection)
600V rms and up to 6,500A (with clamps)
Harmonics (IEC 1000-4-7) display up to 50th order
MIN, MAX, AVERAGE, PEAK and Crest Factor display
W, VA, VAR power, DF, THD, CosΦ
Inrush current measurements – Max instantaneous value; Max RMS half-cycle current value and duration of motor start.
RPM rotation speed
Resistance measurement
Simultaneous recording of all parameters, alarms and motor start up currents.
RS232 direct output to PC
2 wire PT100 temperature probe input
Select AC current probes separately :-
Ampflex A193: 10 to 6500Aac (10Hz to 20kHz) 450mm long flexible probe (rs 236-565)
MN93A: 0.2 to 120Aac (40Hz to 10kHz): Jaw size 20mm dia. (rs 236-559)
IP54 Rated
Power measurement up to 250kW (dependant on clamp selection)
600V rms and up to 6,500A (with clamps)
Harmonics (IEC 1000-4-7) display up to 50th order
MIN, MAX, AVERAGE, PEAK and Crest Factor display
W, VA, VAR power, DF, THD, CosΦ
Inrush current measurements – Max instantaneous value; Max RMS half-cycle current value and duration of motor start.
RPM rotation speed
Resistance measurement
Simultaneous recording of all parameters, alarms and motor start up currents.
RS232 direct output to PC
2 wire PT100 temperature probe input
Select AC current probes separately :-
Ampflex A193: 10 to 6500Aac (10Hz to 20kHz) 450mm long flexible probe (rs 236-565)
MN93A: 0.2 to 120Aac (40Hz to 10kHz): Jaw size 20mm dia. (rs 236-559)
IP54 Rated
Supplied with
Supplied with 6 off AA alkaline batteries, test leads, 4mm test probes, crocodile clips, RS232/USB optical cable and instructions
Specifications
Attribute | Value |
---|---|
Absolute Maximum Current Measurement | 6500 A ac, 1700 A dcA |
Absolute Maximum Power Measurement | 9999 kW, 9999 kVar, 9999kVA |
Number of Phases | 1, 3 |
Maximum Voltage | 600V ac |
Best Voltage Measurement Accuracy | ±0.5% +2 Digits |
Best Current Measurement Accuracy | ±0.1% + 1 Digit |
Display Type | Backlit LCD |
Measurement Type | Current, Energy, Frequency, Harmonics, Inrush Current, Phase rotation, Power, Resistance (winding), RPM, Temperature, Voltage |
Measurement Standards | IEC62301 |
Interface Type | RS232, USB |
Power Source | Battery, Mains |
Battery Type | AA |
Battery Life | 20h |
Model Number p | C.A 8220 |
Weight | 880g |
Maximum Operating Temperature | +50°C |
Dimensions | 211 x 108 x 60mm |
Maximum Frequency | 69Hz |
Length | 211mm |
Width | 108mm |
Minimum Frequency | 40 Hz |
Height | 60mm |
Minimum Operating Temperature | 0°C |
Related links
- Chauvin Arnoux CA 1110 Light Meter 0.1 lx to 200000lx, ±3 %
- Chauvin Arnoux P01102131, Accessory Type Case
- Chauvin Arnoux CA 832 Sound Level Meter, 35dB to 130dB
- Fluke FLUKE-PQ-MARKER, Accessory Type Cable Marker
- Chauvin Arnoux CA 1227 Vane Anemometer, 35m/s Max
- Fluke I1000S, Accessory Type AC Current Probe
- Chauvin Arnoux Energy 3 Phase Backlit LCD Power Monitoring Device,...
- Chauvin Arnoux CA 755 Handheld Digital Multimeter, 1000V ac Max